The Wavecom WCM-RCD-KIT is a comprehensive and reliable solution for testing both portable and fixed RCDs, ensuring safety and compliance in professional environments. Designed to prevent disruption to the mains switchboard, this kit features a digital RCD tester paired with an isolation transformer for uninterrupted and accurate testing. Fully compliant with AS/NZS 3760:2022 standards, it’s ideal for applications where safety and precision are critical.
The included isolation transformer ensures a stable 240V AC supply and prevents tripping of the mains switchboard during testing. CAT III 1000V and CAT IV 600V-rated test leads further enhance safety during direct switchboard testing. The kit also includes a rugged carry case for portability and protection, along with advanced diagnostic features such as faulty earth detection, trip-time readouts, and ramp current testing for comprehensive RCD evaluation.
Q: What is the purpose of the isolation transformer?
A: It prevents tripping of the mains switchboard during testing and ensures a consistent 240V AC supply for accurate results.
Q: What safety standards does this kit comply with?
A: The kit complies with AS/NZS 3760:2022 standards and includes test leads rated to CAT III 1000V and CAT IV 600V.
Q: Is it easy to transport?
A: Yes, the kit comes with a rugged carry case for secure transport, although it does not include a shoulder strap.
Q: What additional features does the RCD tester provide?
A: It offers precise trip current and time measurements, ramp current testing, and faulty earth detection for thorough diagnostics.
(WCM-RCD-KIT)
Warranty starts from Invoice Date
Domestic Use: 1 Year
Commercial Use: 1 Year
Warranty Method: Return to Sparky Direct
Specification | Details |
---|---|
Trip Current Range | 10, 30, 100, 300, 500 & 650mA |
Time Trip | Up to 450ms readout for testing delay action breakers |
Ramp Current Test | 0-650mA depending on range selection |
Voltage Test Range | 240VAC +10%/-6% @ 50Hz |
Trip Test | 0° & 180° Waveform from zero crossing |
Temperature Cut Out | 65°C |
Warning Indicators |
Faulty Earth Detection, Out of Voltage Range, Mains Supply Wiring Condition Monitor |
Power Source | 4 AA Batteries, 20mA Standby Mode |
Auto-Off | Approximately 1 min after no button operation |
Display | 55 x 40 mm, 3 Digit Digital LCD Display |
Operating Temperature | -15°C to 45°C |
Safety | CAT III, 600V - Double Insulated - IP40 - Resistance to mechanical shock up to 1G |
Calibration | 12-month calibration certification, recommended annually |
Dimensions (Tester) | 210 mm x 71 mm x 51 mm |
Dimensions (Case) | 320 mm x 320 mm x 160 mm |
These specifications and characteristics outline physical, mechanical, electrical details.
Brand | Wavecom |
SKU | WCM-RCD-KIT |
Barcode # | 9348707000000 |
Package Weight | 2.910kg |
Package Width | 0.315m |
Package Height | 0.150m |
Package Length | 0.320m |
TYPE | VALUE |
---|---|
Type | Tester |
Brand | Wacecom |
Safety | CAT III, 600V |
Batteries | 4 x AA Batteries |
RCD test | Yes |
Rated Tripping Current | 10/30/100/500/650mA |
Trip Current Duration | 450ms |
Test Voltage | 240V AC +10%/-6% @ 50Hz |